Nusselt Number Calculator

The Nusselt number (Nu) is the dimensionless ratio of convective to conductive heat transfer. Compute it from its definition Nu = h·L/k, from the Dittus–Boelter turbulent-pipe correlation, or from the laminar flat-plate correlation — and convert Nu back into a heat transfer coefficient h.

Nu = h·L / k

Mode 1 — Definition: Nu = h·L/k

Solve in any of the four directions. h is the convective coefficient, L the characteristic length, k the fluid thermal conductivity.

Solve for

Prandtl numbers of common fluids

Approximate values near 20 °C (consistent with Incropera, Fundamentals of Heat and Mass Transfer, App. A). Pr of liquids drops sharply with temperature — treat oil values as order-of-magnitude.

FluidPr (approx)Notes
Mercury0.025Liquid metal — conduction dominates
Air0.71Gases are ≈ 0.7–1.0
Water7.0At 20 °C
Ethanol16Light organic liquid
Ethylene glycol151Antifreeze; upper end of Dittus–Boelter range
Engine oil~10,400At 20 °C; range 100–40,000 — outside Dittus–Boelter validity
Glycerol~11,600Very viscous — momentum diffusivity dominates
Honest limits. Nusselt correlations are empirical fits, not laws of nature — expect ±10–25% vs experiment even inside the stated ranges. Always evaluate fluid properties (k, Pr) at the correct reference temperature (bulk mean for Dittus–Boelter, film temperature for flat plate). Dittus–Boelter needs fully developed turbulent pipe flow (ReD ≥ 10⁴, L/D ≥ 10); for laminar pipe flow Nu tends to a constant (3.66 for constant wall temperature, 4.36 for constant heat flux in a circular tube), not to zero. The flat-plate formula assumes a laminar boundary layer (Rex < 5×10⁵) with no pressure gradient.

What is the Nusselt number?

The Nusselt number (Nu) is the dimensionless ratio of convective to conductive heat transfer across a fluid layer: Nu = h·L/k, where h is the convective heat transfer coefficient, L a characteristic length and k the fluid thermal conductivity. Nu = 1 means pure conduction; larger values mean convection dominates. Example: h = 500 W/m²K, L = 0.02 m, k = 0.6 W/m·K gives Nu = 500×0.02/0.6 = 16.67. Mode 1 of this calculator solves the definition in all four directions (Nu, h, L or k).

What is the difference between the Nusselt number and the heat transfer coefficient?

The heat transfer coefficient h (W/m²K) is a dimensional quantity that depends on the fluid, the flow and the geometry. The Nusselt number is its dimensionless form, Nu = h·L/k, which lets engineers compare convection across different fluids and sizes and build general correlations. Boundary with the sibling tool: the Heat Transfer Coefficient Calculator computes h itself (including U-values and unit conversion); this calculator works with the dimensionless Nu and the correlations that predict it, and can convert Nu back to h via h = Nu·k/L.

What is the Dittus–Boelter equation?

The Dittus–Boelter correlation predicts the Nusselt number for fully developed turbulent flow inside a pipe: Nu = 0.023·Re^0.8·Pr^n, with n = 0.4 when the wall heats the fluid and n = 0.3 when it cools it. Worked example (Mode 2): Re = 20,000, Pr = 7, heating gives Nu = 0.023 × 20000^0.8 × 7^0.4 = 138.23. With k = 0.6 W/m·K and a 0.025 m pipe diameter, that is h = Nu·k/L = 138.2264×0.6/0.025 = 3317.43 W/m²K.

Should I use n = 0.4 or n = 0.3 in Dittus–Boelter?

Use n = 0.4 when the wall is hotter than the fluid (heating: heat flows wall → fluid) and n = 0.3 when the wall is cooler (cooling: fluid → wall). The exponent corrects for how the temperature profile distorts viscosity near the wall. Same flow, different direction: Re = 20,000, Pr = 7 gives Nu = 138.23 for heating but only 113.78 for cooling — about 18% lower, so picking the wrong exponent is a real error, not a rounding one.

When is the Dittus–Boelter correlation valid?

Three conditions: Reynolds number Re ≥ 10,000 (fully turbulent), Prandtl number 0.6 ≤ Pr ≤ 160, and pipe length L/D ≥ 10 so the flow is developed. This calculator shows a warning whenever Re < 10,000 or Pr leaves 0.6–160, and labels the regime (laminar below 2,300, transitional 2,300–10,000, turbulent above 10,000). Gases (Pr ≈ 0.7) and water (Pr ≈ 7) fit comfortably; engine oil (Pr in the thousands) does not — the correlation was never validated there.

What is the flat-plate laminar correlation?

For laminar flow over an isothermal flat plate the local Nusselt number is Nu_x = 0.664·Re_x^(1/2)·Pr^(1/3), valid for Re_x < 5×10^5 and Pr ≥ 0.6. Example (Mode 3): air-like flow at Re_x = 100,000 with Pr = 0.707 gives Nu_x = 0.664 × 100000^0.5 × 0.707^(1/3) = 187.06. Above Re_x ≈ 5×10^5 the boundary layer transitions and this formula underpredicts — the tool warns you.

What is the difference between local and average Nusselt number on a flat plate?

The local Nu_x describes convection at one position x along the plate, while the average Nu over 0→L describes the whole plate (what you need for total heat rate). For a fully laminar plate they are linked exactly: the average equals twice the local value evaluated at Re_L, Nu_bar = 2·Nu_x(Re_L). Example: Re_L = 400,000, Pr = 7 gives an average Nu of 1606.67. Mode 3 reports both numbers so you can use whichever your hand calculation needs.

Where do I find the Prandtl number of my fluid?

Pr depends only on the fluid and its temperature — the reference table on this page covers the common cases: air ≈ 0.71, water ≈ 7.0 (20 °C), ethanol ≈ 16, ethylene glycol ≈ 151, engine oil ≈ 10,400 and glycerol ≈ 11,600. Two cautions: Pr of liquids falls sharply as temperature rises (oils especially — always use the value at your operating temperature), and Dittus–Boelter is only validated up to Pr = 160, so the oil and glycerol presets will trigger the range warning by design.

What units does the Nusselt number use?

None — Nu is dimensionless, so it never needs unit conversion. Only the inputs carry units: h in W/m²K (or BTU/(hr·ft²·°F)), L in m/cm/mm/inch/ft, k in W/m·K (or BTU/(hr·ft·°F)). The calculator converts everything to SI internally; for reference, 100 BTU/(hr·ft²·°F) = 567.83 W/m²K. To get a dimensional coefficient back out, use h = Nu·k/L — Mode 2 does this automatically.

My pipe flow is laminar — can I still use Dittus–Boelter?

No. Dittus–Boelter is strictly a turbulent correlation; below Re ≈ 10,000 (and certainly in laminar flow, Re < 2,300) it extrapolates badly. For fully developed laminar flow in a circular tube the Nusselt number approaches a constant instead: Nu = 3.66 for constant wall temperature, Nu = 4.36 for constant wall heat flux. For the laminar entrance region use a Graetz-type correlation such as Seider–Tate. Check the regime badge in Mode 2 before trusting any number it produces.