Plan a basement finishing project in one place: room area and layout, IRC ceiling-height and egress-window code checks, plus flooring, rigid-foam insulation, recessed-lighting, and paint estimates. 7 modes, 100% in-browser.
Pick a mode, enter your measurements, and get the sizing plus the code verdict.
Measure finished floor to finished ceiling. Example: 6 ft 9 in = 6.75.
Tip: get it from mode 1 (wall area).
IRC 2021 Table N1102.1.2 basement walls: zones 1–2 none; zone 3 R-5/13; zone 4 R-10/13; zones 5–8 R-15/19.
Tip: get it from mode 1 (wall area).
Code figures (R305.1, R310, R304, N1102.1.2) are fixed — they come from the 2021 IRC, not from these defaults.
The figures this tool checks against. Always confirm your local adopted edition — cities and counties can amend them.
| Section | Rule | Figure |
|---|---|---|
| R304.1 / R304.2 | Habitable rooms: minimum area (kitchens excepted); minimum dimension | 70 sq ft · 7 ft |
| R305.1 | Ceiling: habitable spaces | 7 ft (84 in) |
| R305.1 | Ceiling: bathrooms, toilet rooms, laundry rooms | 6 ft 8 in (80 in) |
| R305.1 exc. 3 | Beams, girders, ducts may project to within | 6 ft 4 in (76 in) of finished floor |
| R310.2.1 | Egress: minimum net clear opening (5.0 sq ft at grade floor) | 5.7 sq ft |
| R310.2 | Egress: minimum clear height × width | 24 in × 20 in |
| R310.2.3.2 | Egress: sill height above floor, maximum | 44 in |
| R310.4.1 | Window well: minimum horizontal area; min projection & width | 9 sq ft · 36 in × 36 in |
| R310.4.2 | Window well: ladder or steps required when deeper than | 44 in |
| N1102.1.2 | Basement wall insulation by climate zone (continuous / cavity) | Z1–2: none · Z3: 5/13 · Z4: 10/13 · Z5–8: 15/19 |
Under IRC R305.1, habitable basement spaces — bedrooms, living rooms, hallways — need a finished ceiling height of at least 7 ft (84 in). Bathrooms, toilet rooms, and laundry rooms may be 6 ft 8 in (80 in), and non-habitable basement portions may be 6 ft 8 in as well. Beams, girders, ducts, or other obstructions may project to within 6 ft 4 in (76 in) of the finished floor. Example: a 6 ft 9 in (81 in) ceiling is 3 in short of the 7 ft rule, so it fails for a bedroom — but it passes for a basement bathroom, which needs only 80 in.
IRC R310.2 requires every basement sleeping room to have an emergency escape and rescue opening with a net clear opening of at least 5.7 sq ft — 5.0 sq ft is allowed for at-grade openings — at least 24 in high, at least 20 in wide, and with the sill no more than 44 in above the floor. Example: a window with a 24 in by 41 in clear opening gives 24 × 41 = 984 sq in ÷ 144 = 6.83 sq ft, so it passes all four checks. If the sill is below the adjacent exterior grade, a window well is also required.
Multiply length by width. A 30 ft by 25 ft basement is 30 × 25 = 750 sq ft. The perimeter is 2 × (30 + 25) = 110 ft, and the foundation wall area is 110 ft × 8 ft wall height = 880 sq ft — that wall figure drives insulation, drywall, and paint estimates. Measure the finished (or planned finished) dimensions, and measure each room separately if the basement is divided.
IRC R304 treats a basement bedroom like any habitable room: at least 70 sq ft of floor area (kitchens are excepted) and at least 7 ft in every horizontal dimension. A 10 ft by 7 ft room is 10 × 7 = 70 sq ft with a 7 ft smallest dimension, so it passes both checks. The bedroom also needs a compliant egress window and a 7 ft finished ceiling per R305.1.
Plan on about 350 sq ft per gallon per coat on smooth primed drywall. Example: a 10 ft by 12 ft room with 8 ft ceilings has 2 × (10 + 12) × 8 = 352 sq ft of wall. One coat needs 352 ÷ 350 = 1.006 gal; two coats need 2.01 gal, so buy 2.25 gal (rounded up to the nearest quart). Textured, porous, or unprimed drywall absorbs more — budget roughly 300 sq ft per gallon there.
Aim for 10–20 lumens per sq ft in living areas (about 5–10 for ambient hallways, 30–40 for task zones). Example: a 25 ft by 20 ft room is 500 sq ft; at 15 lumens per sq ft the target is 500 × 15 = 7,500 lumens. With 800-lumen cans you need 7,500 ÷ 800 = 9.4 → 10, laid out as 4 columns × 3 rows = 12 fixtures for an even grid, delivering 12 × 800 = 9,600 lumens — above target. Spacing works out to 25 ÷ 4 = 6.25 ft by 20 ÷ 3 ≈ 6.67 ft on center.
Standard 4 ft by 8 ft sheets cover 32 sq ft each. Example: a 30 ft by 25 ft room with 8 ft walls has 2 × (30 + 25) × 8 = 880 sq ft of wall; with 10% waste that is 880 × 1.10 = 968 sq ft, and 968 ÷ 32 = 30.25 → 31 sheets. For thickness, divide your target R-value by the foam's R per inch: XPS is R-5.0 per inch, so R-15 needs 15 ÷ 5 = 3 in. Polyiso is R-6.5 per inch and EPS is about R-4.2 per inch.
Yes, when the well is deeper than 44 in — IRC R310.4.2 requires a permanently affixed ladder or steps in that case. The well itself must provide at least 9 sq ft of horizontal area with a minimum 36 in horizontal projection and 36 in width, and it must allow the egress window to open fully. A 40 in by 40 in well is 40 × 40 = 1,600 sq in ÷ 144 = 11.11 sq ft, so it passes the area rule.