Size control valves and check existing ones: compute the flow coefficient Cv from flow rate and pressure drop, solve for flow or pressure drop instead, handle compressible gas flow with automatic critical (choked) flow detection, and convert between Cv and Kv.
Cv is the number of US gallons per minute of 60°F water that flows through the valve with a 1 psi pressure drop.
Standard Cv gas sizing equation. When ΔP ≥ P1/2 the flow is choked (critical) and Cv follows the sonic-flow branch automatically.
Kv is the metric flow coefficient (m³/h of water at 1 bar drop). Kv = 0.865 × Cv.
Worked examples (verify them above):
| Case | Inputs | Result |
|---|---|---|
| Water valve | Q = 100 gpm, ΔP = 4 psi, SG = 1 | Cv = 50.0 |
| Forward solve | Cv = 50, ΔP = 4 psi, SG = 1 | Q = 100 gpm |
| Reverse solve | Cv = 50, Q = 100 gpm, SG = 1 | ΔP = 4.0 psi |
| Natural-gas valve | Q = 100,000 SCFH, P1 = 100 psia, P2 = 80 psia, 60°F | Cv ≈ 1.273 (subcritical) |
| Choked gas flow | Q = 50,000 SCFH, P1 = 100 psia, P2 = 40 psia, 60°F | Cv ≈ 0.587 (critical) |
| Metric coefficient | Cv = 50 | Kv = 43.25 |
Cv is the flow capacity rating of a valve: the number of US gallons per minute of 60°F water that flows through the valve with exactly a 1 psi pressure drop. A higher Cv means a less restrictive valve. Use tab 1 above to compute it from a measured flow and pressure drop.
For liquids, Cv = Q × √(SG / ΔP), where Q is flow in gpm, ΔP is pressure drop in psi, and SG is specific gravity relative to water. Example: 100 gpm of water (SG = 1) with a 4 psi drop gives Cv = 100 × √(1/4) = 50.0. Enter your numbers in tab 1 — gpm, L/min and m³/h are all accepted.
Rearrange the definition: Q = Cv × √(ΔP / SG). Example: a valve with Cv = 50 and a 4 psi drop on water passes Q = 50 × √(4/1) = 100 gpm. Tab 2 solves this and reports the answer in gpm, L/min and m³/h.
For liquids, ΔP = SG × (Q / Cv)². Example: Cv = 50 with 100 gpm of water gives ΔP = 1 × (100/50)² = 4.0 psi. Note the squared relationship: doubling the flow quadruples the pressure drop. Tab 3 solves this and converts the answer to psi, bar and kPa.
Multiply by 0.865: Kv = 0.865 × Cv. Example: a valve rated Cv = 50 has Kv = 43.25. Tab 5 does the conversion both ways.
Divide by 0.865: Cv = Kv / 0.865. Example: Kv = 43.25 corresponds to Cv = 50.0. Tab 5 does the conversion both ways.
They measure the same thing in different unit systems. Cv is the US coefficient: gpm of 60°F water at a 1 psi drop. Kv is the metric coefficient: m³/h of water at a 1 bar drop. They are related by Kv = 0.865 × Cv (equivalently Cv ≈ 1.156 × Kv).
Gas is compressible, so the published Cv gas sizing equation is used: with flow Q in SCFH and pressures P1, P2 in psia, Cv = Q / (1360 × P1 × √(ΔP/P1) × √(520/(SG·T·Z))) for subcritical flow. Example: 100,000 SCFH of natural gas (SG 0.6) at P1 = 100 psia, P2 = 80 psia and 60°F gives Cv ≈ 1.273 (subcritical). Tab 4 runs this automatically.
When the pressure drop reaches half the inlet pressure (ΔP ≥ P1/2), gas velocity at the vena contracta hits sonic speed and lowering the outlet pressure further cannot increase flow — the flow is choked. The equation then switches to Cv = Q / (660 × P1 × √(520/(SG·T·Z))). Example: 50,000 SCFH of natural gas at P1 = 100 psia, P2 = 40 psia and 60°F gives Cv ≈ 0.587 in the critical regime. Tab 4 detects the regime for you and labels it.
Yes. Tabs 1–3 accept psi, bar and kPa and convert to psi internally (1 bar = 14.5038 psi, 1 kPa = 0.145038 psi) before applying the formulas. Tab 4 accepts psi, bar or kPa for P1/P2 with an absolute/gauge selector, then converts to psia for the gas equation.
SG is relative to water for liquids (water = 1.0) and relative to air for gases (air = 1.0; natural gas ≈ 0.6, propane ≈ 1.52). Tab 4 offers presets for common gases. For liquids denser than water the same flow needs a larger Cv — for example 60 gpm of a SG 1.2 fluid at 9 psi drop needs Cv ≈ 21.9 instead of 20 for water.
Cv itself is defined at 60°F water, so liquid temperature enters only through density (SG). For gases, temperature matters directly: the gas equation uses absolute temperature in Rankine (°R = °F + 459.67) plus the compressibility factor Z. Tab 4 takes °F and Z as inputs.
It is a solid first step for sizing estimates — but always confirm against the manufacturer's published Cv data and valve curves before buying or installing. Real valves deviate by trim style, and critical-service applications need proper engineering review.