Three Phase Power Calculator
Real power P = √3·VL·IL·PF, apparent power S, reactive power Q, current solver, wye/delta line↔phase conversion, power-factor correction capacitor sizing, and a single-phase comparison — all in one page, 100% in your browser.
Three-phase power from V, I, PF
Enter line-to-line voltage, line current and power factor. Balanced 3-wire/4-wire system assumed.
Line current from power
Solve I = P ÷ (√3·VL·PF) — the reverse of the power formula, e.g. to size breakers and cables.
Power factor correction capacitor
Size the capacitor bank that raises PF from PF₁ to PF₂: Qc = P·(tan φ₁ − tan φ₂).
Line ↔ phase conversion (wye / delta)
Wye: VL=√3·Vph, IL=Iph. Delta: VL=Vph, IL=√3·Iph.
Single-phase vs three-phase comparison
Same real power and PF: compare the current a single-phase supply needs versus a three-phase supply.
Formulas & methodology
All calculations assume a balanced three-phase system (equal phase loads). Line quantities VL, IL are what you measure with a multimeter/clamp meter on the supply conductors.
Wye vs delta reference
| Relation | Wye (Y) | Delta (Δ) |
|---|---|---|
| Voltage | VL = √3 · Vph | VL = Vph |
| Current | IL = Iph | IL = √3 · Iph |
| Neutral | Yes | No |
Worked example
A 400 V, 10 A, PF 0.8 load: P = √3 × 400 × 10 × 0.8 = 5,542.56 W; S = √3 × 400 × 10 = 6,928.20 VA; Q = √(6,928.20² − 5,542.56²) = 4,156.92 var; power angle φ = arccos(0.8) = 36.87°; that is 7.4327 HP.
Scope boundary
This tool covers: three-phase power/current/PF calculations, wye↔delta line/phase conversion, capacitor bank sizing, and 1-phase vs 3-phase comparison.
Not duplicated here: general unit conversion lives in the electrical unit converter; voltage divider, dB and RMS voltage tools live in the voltage converter; conductor sizing by length and ampacity lives in the 12 V wire size calculator.
Frequently asked questions