Motor Capacitor Size Calculator — Run & Start Capacitor Sizing

Size run capacitors from measured motor no-load current, size start capacitors with the 2–4× rule, pick the right voltage rating, and design a discharge bleed resistor. Works for 50 Hz and 60 Hz single-phase motors (PSC, capacitor-start, capacitor-start/run).

Educational tool. Capacitors store a dangerous electrical charge — always discharge before touching, and have a qualified technician do mains work you are not trained for.

⚠ Safety first (read this): a motor capacitor can hold a painful or lethal charge long after power is disconnected. Never short the terminals with a screwdriver. Discharge through a resistor, wait, then verify 0 V with a meter before touching. If anything here is unfamiliar, stop and call a qualified motor technician.

Run capacitor size from no-load current

Enter the motor's no-load current (clamp meter, motor uncoupled from its load), line voltage, and frequency.

Calculated run capacitance:

–

Rule of thumb: a run capacitor's µF must match the motor design (±5–10% tolerance). The VAC rating may be higher, never lower.

C(µF) = I × 10⁶ / (2π × f × V) — the run capacitor / motor capacitor formula from no-load current

Source: Comar Condensatori motor-capacitor catalog (manufacturer datasheet) — the standard industry formula, equivalent to Xc = 1/(2πfC) with Ic = V/Xc. At 60 Hz this reduces to the well-known “2652 rule”: C ≈ 2652.58 × I / V.

Start capacitor sizing (2–4× rule)

Start capacitors are electrolytic, short-duty only (disconnected by a centrifugal switch or relay after ~1–2 s). Size them from the run capacitor value.

Rule-of-thumb band (2×–4× run):

–

Start-capacitor voltage class must be ≥ line voltage (standard classes: 125 / 165 / 250 / 330 V — 250 V is the usual choice for 220–240 V motors). Never run a start capacitor continuously.

C_start ≈ (2 to 4) × C_run → nearest standard EIA RS-463 MFD range — the start capacitor formula

Motor capacitor voltage rating & discharge (bleeder) resistor

Picking the correct motor capacitor voltage rating matters as much as the µF value — underrated capacitors fail violently.

Stored energy for reference: E = ½CV² (see our capacitor energy calculator). Even after the bleed resistor has done its job, always verify 0 V with a meter before touching terminals.

R = t / (5 × C)   ·   P = V² / R

Typical motor capacitor chart (by HP)

Typical values for single-phase capacitor motors at ~230 V (1hp, 2hp, 3hp, 5hp and 10hp motors, 50hz and 60hz). 60 Hz run values follow the standard NEMA application table; 50 Hz run values are ≈20% higher (from the frequency term in the formula). Start ranges are standard EIA RS-463 MFD ranges. Always prefer the motor nameplate.

Motor HPRun µF (60 Hz)Run µF (50 Hz ≈)Start µF range
1/45659–71
1/37.5970–84
1/2101288–108
3/412.515108–130
11518145–174
1½2024161–193
22530189–227
34048270–324
55566378–454
7½8096540–648
10100120800–960

HVAC note: fan motors and compressors often use dual run capacitors (e.g. 40+5 µF) — one can serving two motors. Size each section independently with the run calculator above. Reading this chart answers common questions like "what size capacitor for a 1 HP motor" (≈15 µF run, 145–174 µF start at 60 Hz) or "what size capacitor for a 2 HP motor" (≈25 µF run, 189–227 µF start).

How motor capacitor sizing works

1. Run capacitor — the physics

Why does a single phase motor need a capacitor? A single-phase supply produces a pulsating, not rotating, magnetic field, so the motor cannot start or develop full torque on its own. The capacitor feeds a second (auxiliary) winding with a phase-shifted current, creating the rotating field the rotor needs.

A permanent-split-capacitor (PSC) motor feeds its auxiliary winding through the run capacitor. The capacitor's reactance Xc = 1/(2πfC) sets the auxiliary-winding current Ic = V/Xc, which creates the phase shift the motor needs for torque. Rearranging gives the sizing formula:

C(µF) = I × 10⁶ / (2π × f × V)

Measure I with a clamp meter on the uncoupled (no-load) motor — nameplate full-load current is the wrong number here. Because f sits in the denominator, a 50 Hz supply needs ~20% more µF than 60 Hz for the same current.

2. Start capacitor — the 2–4× rule

Capacitor-start motors need a much larger phase shift for a second or two at startup, so the start capacitor is 2–4× the run value, then a centrifugal switch takes it out of circuit. Because they only see brief duty, start capacitors are non-polarized electrolytics in standard MFD ranges (EIA RS-463), not continuous-duty film types.

3. Voltage ratings

µF must match; VAC may be higher, never lower. Size run capacitors at ≥ 1.5× line voltage (370 VAC minimum, 440 VAC preferred, for 220–240 V systems) because the auxiliary winding can see voltages above line. Start-capacitor classes (125/165/250/330 V) need only cover line voltage briefly — 250 V is standard for 230 V motors.

4. Discharge safety

A capacitor is ~99.3% discharged after five time constants (t = 5RC). A bleeder resistor sized R = t/(5C) across the terminals makes the capacitor safe to handle after the target time — but always verify 0 V with a meter before touching, since bleeders can fail open.

Worked example

A 230 V / 50 Hz motor draws 2.0 A uncoupled (about 15 microfarads per hp at 60 Hz — that is how many microfarads per hp a typical motor needs; see the chart): C = 2 × 10⁶/(2π × 50 × 230) ≈ 27.7 µF → nearest standard 30 µF run capacitor, 370 VAC (440 VAC preferred). Start: 2–4× → 60–120 µF band → nearest standard EIA range containing 3× (90 µF) is 80–100 µF, 250 V class.

Scope boundary. This tool (#442) is the engineering calculator: it derives run capacitance from measured no-load current, frequency and voltage, sizes start capacitors, selects voltage ratings, and designs discharge bleed resistors. Our capacitor-size tool (#398) is the quick HP→table lookup from a standard NEMA chart, and capacitor-energy (#397) computes stored energy (E = ½CV²) and charge. Different inputs, different engines — they complement each other.

Frequently asked questions

What size capacitor does a 1 HP single-phase motor need?
A typical 1 HP single-phase motor uses about 15 µF run capacitance at 60 Hz (about 18 µF at 50 Hz) and a 145–174 µF start capacitor (standard EIA RS-463 range). Always check the motor nameplate first — the nameplate value overrides any calculator or chart.
How to calculate run capacitor size from no-load current?
Use C(µF) = I × 10⁶ / (2π × f × V), where I is the motor no-load current in amps, f is the supply frequency in Hz, and V is the supply voltage in volts. Measure the no-load current with a clamp meter with the motor uncoupled, then pick the nearest standard capacitor value.
What is the 2652 rule for run capacitors?
At 60 Hz the formula simplifies to C(µF) ≈ 2652.58 × I / V — so at 230 V you need about 11.5 µF per amp of no-load current. At 50 Hz the constant is 3183.10, giving about 13.8 µF per amp at 230 V. It is a quick sanity check, not a replacement for the nameplate value.
How do you size a start capacitor?
The rule of thumb is 2 to 4 times the run capacitor value. For a 15 µF run capacitor that means 30–60 µF; pick the nearest standard EIA RS-463 start range, e.g. 40–50 µF. Start capacitors are electrolytic and rated for short duty only — never leave one energized continuously.
Can I use a run capacitor with higher µF than specified?
Stay within about ±5–10% of the specified value. A moderately oversized run capacitor raises auxiliary-winding current, which increases heat and shortens motor and capacitor life. If in doubt, match the nameplate value exactly.
Can I use a capacitor with a higher voltage rating?
Yes — the voltage rating may always be equal or higher, never lower. A 440 VAC run capacitor is a fine substitute for a 370 VAC one of the same µF. Choose a run-capacitor VAC rating of at least 1.5× the line voltage (370 VAC minimum for 230 V systems).
What is the difference between a run capacitor and a start capacitor?
A run capacitor is a film (usually polypropylene) capacitor designed for continuous duty — it stays energized the whole time the motor runs (typically 1.5–100 µF, 370/440 VAC). A start capacitor is a non-polarized electrolytic capacitor (typically 25–550+ µF) that is only in circuit for a second or two at startup, then disconnected by a centrifugal switch or relay.
What are the symptoms of a bad or undersized run capacitor?
A motor that hums but will not start, slow or no start, the motor overheating, higher than normal running current, tripped overloads, and reduced torque. A failed capacitor often looks swollen or leaks. Test with the power off and the capacitor fully discharged, or have a technician test it.
How do I safely discharge a motor capacitor?
Disconnect all power and wait, then discharge through a resistor (for example a 15–20 kΩ, 2 W resistor) held with insulated probes for at least 60 seconds — never short the terminals with a screwdriver, which can damage the capacitor and throw sparks. Verify 0 V with a meter before touching. If you are not trained, have a qualified technician do it.
Should I choose a 370 V or 440 V run capacitor?
Both work if the µF matches; 440 VAC simply has more voltage margin and usually a longer life. For 220–240 V mains the minimum is 370 VAC, so 440 VAC is the preferred, longer-lasting choice.
Do three-phase motors need run capacitors?
No. Three-phase motors create their own rotating magnetic field from the three-phase supply and do not need start or run capacitors. This calculator is for single-phase induction motors only (PSC, capacitor-start, and capacitor-start/capacitor-run types).
How does this differ from the capacitor-size chart tool?
The capacitor-size tool on nrtechstudio.com is a quick horsepower-to-table lookup using a standard NEMA application chart. This motor-capacitor-size tool is the engineering calculator: it derives run capacitance from your measured no-load current, frequency and voltage, sizes the start capacitor, selects voltage ratings, and designs the discharge bleed resistor.
Does 50 Hz vs 60 Hz change the capacitor size?
Yes. Capacitive reactance Xc = 1/(2πfC) depends on frequency, so at 50 Hz you need about 20% more capacitance than at 60 Hz for the same current and voltage (3183 vs 2652 constant). A motor nameplated for 60 Hz should be re-checked, not blindly fitted, when run on 50 Hz.
When should I call a technician instead of replacing a capacitor myself?
Call a qualified technician if you are unsure which capacitor type your motor uses, if the motor trips breakers, smells burnt, or has damaged windings, or if you are not comfortable verifying zero voltage with a meter. Capacitors store a dangerous charge and mains wiring mistakes can destroy the motor or injure you.

Related motor capacitor sizing topics

This page covers the searches people run when a single-phase motor will not start or a capacitor has failed: single phase motor capacitor calculator, electric motor capacitor calculator, PSC motor capacitor size, capacitor start capacitor run sizing, dual run capacitor size (such as 40+5 µF), HVAC, compressor, fan motor, well pump and pool pump capacitor sizing, 370V vs 440V run capacitor choice, start capacitor voltage rating, how to safely discharge a motor capacitor, and bleed resistor sizing. Use the calculators above for your exact numbers — the chart is only a starting point when the nameplate is unreadable.