⚡ 3-Phase Network Lab

Delta to Wye (Δ-Y) Conversion Calculator

Convert three-phase impedances between delta (Δ) and wye (Y/star) connections — balanced networks via ZY = ZΔ/3, unbalanced networks via the full Δ-Y transformation, plus resistor/inductor/capacitor networks at any frequency and line↔phase voltage/current relationships.

100% client-side — your numbers never leave this browser

Δ Delta

A B C Zca Zab Zbc
Δ branches: —

Y Wye (star)

N A B C Za Zb Zc
Y arms: —

1Balanced Δ ↔ Y Converter

All three branches identical: ZY = ZΔ / 3 and ZΔ = 3 × ZY. Works for resistors, and for inductors/capacitors at any frequency (XL = 2πfL, XC = 1/2πfC).

Equivalent value
—
Enter values and hit convert.

2Unbalanced Δ → Y

Three different delta branches (resistances): Za = Zab·Zca/Σ, Zb = Zab·Zbc/Σ, Zc = Zbc·Zca/Σ, with Σ = Zab+Zbc+Zca.

Equivalent wye
—
Enter three branch values and hit convert.

3Unbalanced Y → Δ

Three different wye arms (resistances): with N = ZaZb + ZbZc + ZcZa, then Zab = N/Zc, Zbc = N/Za, Zca = N/Zb.

Equivalent delta
—
Enter three arm values and hit convert.

4Line ↔ Phase Voltage, Current & Power

Wye: VL = √3·Vph, IL = Iph · Delta: VL = Vph, IL = √3·Iph · Power: S = √3·VL·IL, P = S·cos φ, Q = S·sin φ.

Phase values
—
Enter line values and hit calculate.

Methodology

The Δ-Y (delta-wye) transformation replaces a three-terminal network by an equivalent one that presents identical impedance between every pair of terminals. The outside circuit cannot tell the two apart — the conversion is exact for linear lumped impedances at a given frequency.

Balanced: ZY = ZΔ / 3  ·  ZΔ = 3 × ZY
Unbalanced Δ→Y: Σ = Zab+Zbc+Zca; Za=ZabZca/Σ, Zb=ZabZbc/Σ, Zc=ZbcZca/Σ
Unbalanced Y→Δ: N = ZaZb+ZbZc+ZcZa; Zab=N/Zc, Zbc=N/Za, Zca=N/Zb
Reactance: XL = 2πfL  ·  XC = 1/(2πfC)
Wye: VL=√3·Vph, IL=Iph · Delta: VL=Vph, IL=√3·Iph · S=√3·VL·IL

How to convert delta to wye

Every delta to wye conversion starts with one question: are the three branches identical? If yes, the delta to wye conversion formula is one division — this delta to wye calculator shows each step. If the branches differ, you need the full unbalanced delta to wye transformation (tab 2).

  1. Read the three delta branch impedances Zab, Zbc, Zca (or one value for a balanced delta to wye network).
  2. Balanced: divide by 3 → ZY. That is the entire delta to wye conversion.
  3. Unbalanced: form the sum Σ, then each wye arm is the product of its two adjacent delta branches over Σ.
  4. Reversing direction? The wye to delta conversion formula is multiply-by-3 (balanced) or the N-formula (unbalanced, tab 3).

Searching for a delta to wye conversion calculator, a delta to star conversion calculator, or a y-delta transformation calculator? Tab 1 handles the balanced delta wye transform, tabs 2–3 the unbalanced delta-wye transformation. Star to delta conversion is the same math with the names swapped — "star" and "wye" are synonyms, as are "Δ" and "delta". A star delta conversion calculator three phase query and a delta to wye impedance calculator query both land on the same formulas above.

Worked examples (hand-verified)

Example 1 — Balanced: 60 Ω Δ → Y

ZY = 60 / 3 = 20 Ω. Each wye arm is 20 Ω. Check: delta terminal resistance = 60‖120 = 40 Ω; wye terminal resistance = 20 + 20 = 40 Ω. Identical — the networks are equivalent.

Example 2 — Unbalanced: 30 / 60 / 90 Ω Δ → Y

Σ = 30 + 60 + 90 = 180. Za = 30×90/180 = 15 Ω, Zb = 30×60/180 = 10 Ω, Zc = 60×90/180 = 30 Ω. Reverse check with tab 3: N = 15×10 + 10×30 + 30×15 = 900, giving Zab = 900/30 = 30, Zbc = 900/15 = 60, Zca = 900/10 = 90 Ω — the original delta.

Example 3 — Inductor: 90 mH Δ @ 50 Hz → Y

XL = 2π × 50 × 0.09 = 28.27 Ω per delta branch. XY = 28.27 / 3 = 9.42 Ω, i.e. an equivalent LY = 90/3 = 30 mH. Same scaling works for delta wye inductor capacitor networks: a 100 µF delta capacitor @ 50 Hz has XC = 31.83 Ω → wye XC = 10.61 Ω → CY = 3 × 100 = 300 µF (capacitance triples because XC = 1/2πfC must shrink).

Example 4 — 400 V wye: line vs phase

Vph = 400/√3 ≈ 230.9 V, Iph = IL = 10 A. With cos φ = 0.8: S = √3 × 400 × 10 ≈ 6.93 kVA, P = 5.54 kW, Q ≈ 4.16 kVAR. In delta at the same line values, Vph = 400 V and Iph = 10/√3 ≈ 5.77 A, with identical S, P, Q — total three-phase power is connection-independent.

Line voltage vs phase voltage, at a glance

ConnectionVoltageCurrentNeutral
Wye (Y/star)VL = √3 × VphIL = IphYes — common node N
Delta (Δ)VL = VphIL = √3 × IphNo — closed triangle

These wye delta voltage current relationships are why delta connection to wye connection conversions matter in power work: a 3 phase delta to wye analysis of a motor or transformer winding changes which voltage each impedance actually sees. The classic trap: measuring 400 V line-to-line and assuming each delta branch sees 230 V — it sees the full 400 V.

Derivation of ZY = ZΔ/3

Equate the resistance between terminals A and B in both networks. In the balanced delta, current entering A splits through ZΔ directly and through the series pair 2ZΔ: parallel of ZΔ and 2ZΔ is (2/3)ZΔ. In the balanced wye, A-to-B passes through two arms in series: 2ZY. Setting them equal: 2ZY = (2/3)ZΔ → ZY = ZΔ/3. This delta to wye derivation uses only series/parallel equivalence, so it holds for any linear impedance — the same steps convert a delta wye resistor network or an identical-inductor network.

⚠ Honest limitations

  • Magnitude-only for unbalanced networks. The unbalanced tabs accept resistances (real impedances). The general transformation also holds for complex impedances, but phasor (R+jX) arithmetic per branch is not implemented — use the balanced tab for reactive networks.
  • Linear, lumped, single frequency. Nonlinear elements (diodes, saturating cores) and frequency-dependent parasitics break the equivalence.
  • Inductor/capacitor tabs assume ideal parts. Real coils have winding resistance (ESR); real capacitors have ESR and leakage. Results are the ideal-equivalent values.
  • Balanced-reactive shortcut. LY = LΔ/3 and CY = 3·CΔ are exact only when all three branches are identical parts.

🔀 Which calculator do you need?

  • This lab — three-phase Δ-Y / Y-Δ impedance conversion, line↔phase, three-phase power.
  • Amps to Ohms calculator — Ohm's law with AC single/three-phase and wire voltage-drop analysis.
  • Amps to kW calculator — current-to-power conversions including three-phase.
  • Volts to Ohms calculator — DC resistance solver, voltage dividers, resistor color codes.

Frequently asked questions

What is the delta to wye conversion formula?

For a balanced three-phase network, ZY = ZΔ / 3 — divide each delta branch impedance by 3 to get the equivalent wye impedance. Reversing it, ZΔ = 3 × ZY. So a 60 Ω balanced delta becomes a 20 Ω wye, and a 10 Ω wye becomes a 30 Ω delta. These are the delta to wye conversion formula and the wye to delta conversion formula for balanced systems.

How do you convert delta to wye step by step?

If the network is balanced (all three delta branches identical), divide one branch value by 3 — done. If it is unbalanced, use the general delta-wye transformation: Za = Zab × Zca / (Zab + Zbc + Zca), Zb = Zab × Zbc / (sum), Zc = Zbc × Zca / (sum). Tab 1 of the calculator above handles the balanced delta to wye conversion; tab 2 handles the unbalanced case with every step shown.

What is the formula for unbalanced delta to wye conversion?

With delta branches Zab, Zbc, Zca and their sum S = Zab + Zbc + Zca: Za = Zab × Zca / S, Zb = Zab × Zbc / S, Zc = Zbc × Zca / S. Each wye arm equals the product of the two adjacent delta branches divided by the sum of all three. Example: 30, 60, 90 Ω delta (S = 180) gives Za = 15, Zb = 10, Zc = 30 Ω.

How do you convert wye to delta?

Balanced: multiply each wye impedance by 3 (ZΔ = 3 × ZY). Unbalanced: with N = Za×Zb + Zb×Zc + Zc×Za, compute Zab = N / Zc, Zbc = N / Za, Zca = N / Zb. Each delta branch equals the sum of pairwise wye products divided by the opposite wye arm. Example: 15, 10, 30 Ω wye gives N = 900, so Zab = 30, Zbc = 60, Zca = 90 Ω.

Why does dividing by 3 work in delta to wye conversion?

It follows from equating terminal resistances. In a balanced delta, the resistance between any two terminals is one branch in parallel with the series pair of the other two: ZΔ || 2ZΔ = (2/3)ZΔ. In a balanced wye, the resistance between two terminals is 2ZY. Equating them gives 2ZY = (2/3)ZΔ, so ZY = ZΔ / 3. The derivation works for any linear impedance (resistance, reactance), not just resistors.

What is the difference between delta and wye connections?

A delta (Δ) connection wires three branches into a closed triangle with no neutral — each branch sits directly across line-to-line voltage, and line current is √3 times branch current. A wye (Y, star) connection ties one end of each branch to a common neutral node — each branch sees line-to-neutral voltage (VL/√3), and line current equals branch current. Delta is common in motors and heavy loads; wye is standard for distribution because it provides a neutral.

When should I use wye instead of delta?

Use wye when you need a neutral point for single-phase loads or grounding (typical distribution: 400 V line-to-line / 230 V line-to-neutral in wye). Use delta when the load is purely three-phase with no neutral needed, or when you want a winding to circulate third-harmonic currents (transformer delta tertiaries). For analysis, convert whichever one you have into the one that matches the rest of your circuit model.

What is the line voltage vs phase voltage relationship in wye and delta?

Wye: Vline = √3 × Vphase and Iline = Iphase. Delta: Vline = Vphase and Iline = √3 × Iphase. So on a 400 V three-phase wye supply, each phase sees 400/√3 ≈ 230.9 V; on a 400 V delta supply, each branch sees the full 400 V but carries only Iline/√3. Tab 4 of this calculator computes all of these plus three-phase apparent, real, and reactive power (S, P, Q).

Can this calculator convert resistor networks from delta to wye?

Yes — resistor networks are the classic case. Enter the three delta resistor values in tab 2 (or a single value in tab 1 for a balanced resistor network) and it returns the equivalent wye resistors. This is the same transformation used in circuit analysis to simplify bridge-like three-phase and mesh networks, where the delta wye resistor network conversion reduces a loop into a star that is easier to solve.

How do inductor and capacitor networks convert between delta and wye?

The same scaling rules apply, because a balanced branch impedance scales as a whole: a delta inductor becomes LY = LΔ / 3 (reactance XL = 2πfL drops by 3×), and a delta capacitor becomes CY = 3 × CΔ (capacitance triples because XC = 1/(2πfC) must drop by 3×). In tab 1, pick Inductor or Capacitor, enter the component value and frequency, and the calculator shows both the reactance and the equivalent component value.

Is the delta-wye transformation exact or an approximation?

It is exact for linear lumped impedances at a given frequency — the two networks present identical impedance between every pair of external terminals, so the rest of the circuit cannot tell them apart. It is not exact if the branches are nonlinear (diodes, saturating inductors) or if frequency-dependent parasitics differ between the branches, because then the branch impedances are not the single values you entered.

What is a star-delta starter and how is it related?

A star-delta (wye-delta) starter is a motor control method that starts a three-phase induction motor with its windings in wye and then switches to delta for running. In wye, each winding sees 1/√3 of line voltage, so starting current and torque drop to about 1/3 of the delta values — a gentler start. Once up to speed, the contactors switch to delta for full torque. The voltage ratios come from exactly the wye vs delta relationships computed in tab 4.

What are real-world examples of delta to wye conversion?

Common examples: (1) motor winding analysis — three-phase motor impedances are often delta-connected but easier to analyze per-phase in wye; (2) power transformers — converting between Dy and Yy vector groups during short-circuit studies; (3) simplifying PCB or filter networks with delta resistor loops into equivalent wye networks; (4) fault analysis — unbalanced wye loads (e.g. 15/10/30 Ω) are often converted to delta to compute line currents.

Which tab should I use for balanced vs unbalanced networks?

Use the Balanced tab when all three branches are identical — it needs just one value and also supports inductor/capacitor networks with frequency. Use the Unbalanced Δ→Y tab when the three delta branches differ (three inputs), and the Unbalanced Y→Δ tab for the reverse direction. Use the Line/Phase tab when you do not need impedance conversion at all, just Vline vs Vphase, Iline vs Iphase, and three-phase power.

Does this calculator handle three-phase power calculations?

Yes. Tab 4 takes line voltage, line current, and power factor and computes phase voltage, phase current (for wye or delta), apparent power S = √3 × VL × IL, real power P = S × cos φ, and reactive power Q = S × sin φ. Example: 400 V, 10 A, 0.8 pf gives S ≈ 6.93 kVA, P ≈ 5.54 kW, Q ≈ 4.16 kVAR — identical total power in either connection, since power is connection-independent.

Is my data private when I use this calculator?

Yes. This tool is 100% client-side: every calculation runs in your browser with plain JavaScript, and nothing you type is sent anywhere — there is no server, no tracking request, and no data leaves the page. You can verify this in your browser's network panel or disconnect from the internet and keep calculating.

Free tool by NRTechStudio